1.    Portable Extinguishers

• Check the extinguishing medium and applied pressure and refill when needed. • Check the mechanical functions of all components.
• Check if the extinguishers are located in designated place.
• Check the handle and its function.
• Check the hose condition.
• Check the weight of the extinguisher

2.    Fire Pumps.

• Check the fire pump system visually to assure that device appears to be in normal and operational condition.
• Record the pressure on fire pump gauges at Discharge line and suction line.
• Check for automatic indication of controller lights.
• Check all the valves for their respective open/close position.
• Simulate and operate the pump for 10 minutes and check the followings:
a)    Record pressures at Discharge line and Suction line
b)    Confirm the operation of pressure switch.
c)    Observe any excessive vibration or abnormal noise.
d)    Inspect the pump bearing & casing for over heating.
• Check fuel tank level.• Changing the diesel pump oil annually.

3.    Fire Suppression Systems.

Inspect the system for any physical damages.

• Check the cylinders gauges are showing normal pressure and adequate gas quan¬tity.
• Verify the system nozzles are in place.
• Testing the cross zoning signal from smoke detectors.
• Check the function of manual release push button.
• Cleaning the smoke detectors every visit.
• Check the function of the solenoid valve without discharge the gas. • Check fist stage operation.
• Check second stage operation.
• Inspect the system pipes and fittings for any damages and if they are prop erly aligned.
• Testing the system by actuating false alarm for the fire extinguishing panel in order to check the two stages function without discharging the gas.

4.    Automatic Sprinkler System

• Inspect pipe hangers if it is damaged, loose or missing.
• Inspect pipes and fittings to ensure it is free of leaks, not painted, not rusty, no damages and all are properly aligned.
• Check for any obstruction to spray nozzles.
• Check if spare sprinklers and respective zone pipe wrench is available.
• Check all Zone Control Valves by checking the followings:
a)    Condition of Butterfly Valve.
b)    Function of Water Flow Detector (Flow Switch) c)Condition of Test and Drain Valve
• Check and record main supply water pressure.
• Make sure pressure gauges are in good condition and the reading within the range.
• Testing the response for Fire Alarm system, incase of operating the Flow Switch valves.

5. Pre - Action I Deluge Systems


• Check & Record the main supply pressure
• Check and record the pressure of air in the system.
• Check & record the pressure on the push rod chamber.
• Inspect all control valves to verify that all are at proper position and all are supervised.
• Check all valves for any leakage.
• Inspect the deluge valve to verify the following:
a)    The valve is free of physical damages.
b)    The valve is not leaking.
c)    The trim valves are at proper position.
• Ensure system pressure is within the normal range.
• Inspect the system pipes and fittings for any damages and if they are properly aligned.
• Inspect hangers' conditions if it is rusty, loose damaged or missing.
• Inspect all system alarms for proper operation and free from physical damages.

6. Pre - Action I Deluge Systems

• Check & Record the main supply pressure
• Check and record the pressure of air in the system.
• Check & record the pressure on the push rod chamber.
• Inspect all control valves to verify that all are at proper position and all are supervised.
• Check all valves for any leakage.
• Inspect the deluge valve to verify the following:
a)    The valve is free of physical damages.
b)    The valve is not leaking.
c)    The trim valves are at proper position.
• Ensure system pressure is within the normal range.
• Inspect the system pipes and fittings for any damages and if they are properly aligned.
• Inspect hangers' conditions if it is rusty, loose damaged or missing.
• Inspect all system alarms for proper operation and free from physical damages.
 

Product's Overview

Leader Safety and Security. We specialize in Engineered Fire Protection systems utilizing clean agents such as CO2, FM-200, Inergen FE-13, and Water Mist. Our in house engineering department has been factory trained to design and install all of the above systems.. Here are the following systems which Leader Safety & Security installing & maintaining currently.